Components

Removal
Inspection

Hint:
The valve opening temperature is inscribed on the thermostat.

Standard valve opening temperature: 80 to 84°c (176 to 183°f)
If the valve opening temperature is not as specified, replace the thermostat.

Standard valve lift: 10 mm (0.39 In.) Or more at 95°c (203°f)
If the valve lift is not as specified, replace the thermostat.
If it is not fully closed, replace the thermostat.
Installation

Hint:
The jiggle valve may be set to within 10° on either side of the prescribed position.
Torque: 9.0 N*m (92 kgf*cm, 80 in.*Lbf)

Installation
Cooling fan motorBrake warning light does not come on
Wiring diagram
Refer to the brake warning light circuit (see page bc-145).
Inspection procedure
Check can communication system
Check if the can communication system dtc is output
(see page ca-34).
Result
Perform active test by intelligent tester (brake warning light)
...
Adjustment procedure
To select a mirror to adjust,
press the switch.
Left
Right
To adjust the mirror, press the
switch.
Up
Right
Down
Left
...
Installation
Hint:
Use the same procedures for the rh side and lh side.
The procedures listed below are for the lh side.
Install front door belt moulding
assembly lh
Attach the claws to install the belt moulding.
Hint:
Confirm that the moulding is firmly installed.
Install outer r ...