![]()
Description
The no. 1 Cooler thermistor (evaporator temperature sensor) is installed on the evaporator in the air conditioning unit to detect the temperature of the cooled air that has passed through the evaporator and to control the air conditioner. It sends signals to the air conditioning amplifier. The signals change in accordance with the resistance of the no. 1 Cooler thermistor (evaporator temperature sensor). As the temperature decreases, the resistance increases. As the temperature increases, the resistance decreases. The air conditioning amplifier applies a voltage (5 v) to the no. 1 Cooler thermistor (evaporator temperature sensor) and reads voltage changes as changes in the resistance of the no. 1 Cooler thermistor (evaporator temperature sensor). This sensor is used for frost prevention.

Wiring diagram

Inspection procedure

Ok: the display is as specified in the normal condition column.




Standard resistance
Notice:
Hint:
As the temperature increases, the resistance decreases (see the graph).

Standard resistance 

Replace air conditioning amplifier
Ambient temperature sensor circuit
Compressor lock sensor circuitInstallation
Install fuel filler opening lid lock retainer
Install the lock retainer and turn it counterclockwise
as shown in the illustration.
Install fuel filler opening lid lock retainer
Install the cable and turn it clockwise as shown in
the illustration.
Install the fuel l ...
Installation
Hint:
Use the same procedures for the rh side and lh side.
The procedures listed below are for the lh side.
Install front door belt moulding
assembly lh
Attach the claws to install the belt moulding.
Hint:
Confirm that the moulding is firmly installed.
Install outer r ...
Problem symptoms table
When a "normal" code is output during a dtc check but
the problem is still occurring, use the problem symptoms
table. The suspected areas (circuits or parts) for each
problem symptom are in the table. The suspected areas
are listed in order of probability. A description of each of
the ...