Components

Removal
Inspection

Hint:
The valve opening temperature is inscribed on the thermostat.

Standard valve opening temperature: 80 to 84°c (176 to 183°f)
If the valve opening temperature is not as specified, replace the thermostat.

Standard valve lift: 10 mm (0.39 In.) Or more at 95°c (203°f)
If the valve lift is not as specified, replace the thermostat.
If it is not fully closed, replace the thermostat.
Installation

Hint:
The jiggle valve may be set to within 10° on either side of the prescribed position.
Torque: 9.0 N*m (92 kgf*cm, 80 in.*Lbf)

Installation
Cooling fan motorAir mix control servo motor (for automatic air conditioning system)
Components
Removal
Remove air conditioning unit
Remove the air conditioning radiator (see page ac-
185).
Remove air mix control servo motor (see
page ac-191)
Inspection
Inspect air mix control servo motor
Inspect the servo motor operation.
Connect ...
Problem symptoms table (2006/01- )
Hint:
Use the table below to help determine the cause of the
problem symptom. The potential causes of the symptoms are
listed in order of probability in the "suspected area" column
of the table. Check each symptom by checking the suspected
areas in the order they are listed. Replace p ...
Stuck in deceleration sensor
Description
The skid control ecu receives signals from the yaw rate and deceleration
sensor via the can
communication system.
The yaw rate sensor has a built-in deceleration sensor and detects the vehicle's
condition using 2 circuits
(gl1: g sensor 1, gl2: g sensor 2).
If there is t ...