![]()
Description
This dtc is output when the refrigerant pressure is either extremely low (0.19 Mpa [2.0 Kgf/cm2, 28 psi] or less) or extremely high (3.14 Mpa [32.0 Kgf/cm2, 455 psi] or more). The air conditioning pressure sensor, which is installed on the pipe of the high pressure side, detects the refrigerant pressure and sends refrigerant pressure signals to the air conditioning amplifier. The air conditioning amplifier determines the pressure from the signals in accordance with the sensor characteristics, and controls the compressor accordingly.

Wiring diagram

Inspection procedure



Hint:
*: If the ambient temperature is higher than usual but cooling is sufficient, bubbles in the sight glass are permissible.



Ok: the display is as specified in the normal condition column.




Standard resistance



Standard resistance 
Standard voltage 


Then connect the voltmeter's positive (+) lead to terminal 2 and the negative (-) lead to terminal 1. Measure the voltage.
Ok: the voltage changes in accordance with the refrigerant pressure as shown in the graph.


Replace air conditioning amplifier
Compressor lock sensor circuit
Solar sensor circuit (driver side)Diagnosis system
Check dlc3
The ecm uses iso 15765-4 for communication. The
terminal arrangement of the dlc3 complies with sae
j1962 and matches the iso 15765-4 format.
If the result is not as specified, the dlc3 may have a
malfunction. Repair or replace the harness and
connector.
Hint:
Conn ...
Air mix control servo motor (for automatic air conditioning system)
Components
Removal
Remove air conditioning unit
Remove the air conditioning radiator (see page ac-
185).
Remove air mix control servo motor (see
page ac-191)
Inspection
Inspect air mix control servo motor
Inspect the servo motor operation.
Connect ...
Air inlet damper control servo motor circuit
Description
The damper servo (air inlet control) sends pulse signals to indicate the
damper position to the air
conditioning amplifier. The air conditioning amplifier activates the motor
(normal or reverse) based on
these signals to move the air inlet control damper to the appropriate pos ...