Toyota RAV4 (XA40) 2013-2018 Service Manual: Replacement
- discharge refrigerant from refrigeration system
- Start up the engine.
- Turn the a/c switch on.
- Operate the cooler compressor with an engine
speed of approximately 1,000 rpm for 5 to 6 minutes
to circulate the refrigerant and collect the
compressor oil remaining in each component into
the cooler compressor.
- Stop the engine.
- Using sst, discharge the refrigerant gas.
Sst 07110-58060 (07117-58060, 07117-58070,
07117-58080, 07117-58090, 07117-78050,
07117-88060, 07117-88070, 07117-88080)
- Charge refrigerant
- Perform vacuum purging using a vacuum pump.
- Charge refrigerant hfc-134a (r134a).
Standard:
430 +-30 g (15.2 +-1.1 Oz.)
Sst 07110-58060 (07117-58060, 07117-58070,
07117-58080, 07117-58090, 07117-78050,
07117-88060, 07117-88070, 07117-88080)
Notice:
- Do not operate the cooler compressor before
charging refrigerant as the cooler
compressor will not work properly without
any refrigerant, and will overheat.
- Approximately 100 g (3.53 Oz.) Of refrigerant
may need to be charged after bubbles
disappear. The refrigerant amount should be
checked by measuring its quantity, and not
with the sight glass.
- Warm up engine
- Warm up the engine at less than 1,850 rpm for 2
minutes or more after charging the refrigerant.
Notice:
Be sure to warm up the compressor when
turning the a/c switch on after removing and
installing the cooler refrigerant lines (including
the compressor), to prevent damage to the
compressor.
- Check for leakage of refrigerant
- After recharging the refrigerant gas, check for
refrigerant gas leakage using a halogen leak
detector.
- Perform the operation under these conditions:
- Stop the engine.
- secure good ventilation (the gas leak detector
may react to volatile gases other than refrigerant,
such as evaporated gasoline or exhaust gas).
- Repeat the test 2 or 3 times.
- Make sure that some refrigerant remains in the
refrigeration system. When compressor is off:
approximately 392 to 588 kpa (4 to 6 kgf/cm2, 57
to 85 psi)
- Using a gas leak detector, check the refrigerant line
for leakage.
- If a gas leak is not detected on the drain hose,
remove the blower motor control (blower resistor)
from the cooling unit. Insert the gas leak detector
sensor into the unit and perform the test.
- Disconnect the connector and leave the pressure
switch on for approximately 20 minutes. Bring the
gas leak detector close to the pressure switch and
perform the test.
Inspect refrigerant pressure with
manifold gauge set
This method uses a manifold gauge set to locate
problem areas. Read the manifold gauge pressure
when these conditions are establishe ...
Components (2005/11-2006/01)
Components (2006/01- )
...
Other materials:
Seat heater switch
Components
Removal
Disconnect cable from negative battery
terminal
Caution:
Wait at least 90 seconds after disconnecting the
cable from the negative (-) battery terminal to
prevent airbag and seat belt pretensioner activation.
Remove switch base (see page ip-18)
Remove seat he ...
Evaporative emission leak detection pump
Dtc summary
Hint:
The leak detection pump is built into the canister pump module.
Description
The description can be found in the evap (evaporative emission) system (see
page es-335).
Inspection procedure
Refer to the evap system (see page es-340).
Monitor description
5 Hours* afte ...
Circuit opening relay
On-vehicle inspection
Disconnect cable from negative battery
terminal
Caution:
Wait at least 90 seconds after disconnecting the
cable from the negative (-) battery terminal to
prevent airbag and seat belt pretensioner activation.
Inspect instrument panel junction block
Notice:
Th ...